8.11.14 Night Shift Activities

Mp#13-Fuse blown control issue.
This problem originated from day shift where the power supply had a fuse holder melted.

There was an additional 10amp fuse blown with a fault indicating that the purge sheild LS99 was not made.

Upon replacing the fuse everything seemed fine until the pump motor was started. 

After a few minutes of pump run time the fuse would blow again.  Reviewing the schematics revealed the "CE" solenoid is energized through a motor starter contact.

Found "CE" solenoid was bad. Replaced it with spare from uninventoried parts. O.K. to run.